Go to the Home Page Click here for sitemapClick here for sitemap Click here for sitemap  
     

 

[xStart logo]DIL L – Safe Switching of Lamp Loads

[picture of DIL L unit and lamp]The xStart range has been extended by an additional device the contactor DIL L for lighting loads. The DIL L has been developed on the basis of the contactor DIL M and has been optimised for switching lamps.

The high switching capacity masters the inrush currents associated with all kinds of lamps.

The box terminal enables the connection of larger conductor cross-sections in order to facilitate long distances.

Base units 3-pole

AC  24 V 50 Hz  ·  230 V 50 Hz   240 V 60 Hz  ·  400 V 50 Hz   440 V 60 Hz

Part Number
(complete using above voltages):
DILL12(...)DILL18(...)DILL20(...)
Rated operational current IeA274045
(AC1, conventional free air thermal current at 40° C 380 V, 400 V)
Lighting load
Filament lampA142127
Hybrid lampsA121623
Fluorescent lampsA202635
Electronic upstream deviceA121820
High-pressure mercury-arc lampsA121820
Halogen metal vapour lampA121820
Sodium metal vapour arc lampsA121820
Low-pressure sodium lampsA7.51012
Maximum permissible compensation capacityµF470470470

top

This page last updated: 12 July 2007